Good price  online

products details

Created with Pixso. Home Created with Pixso. Products Created with Pixso.
Environmental Testing Equipment
Created with Pixso. EN 1568 High,Medium,Low-expansion foam liquid foaming multiple and liquid separation time measuring instrument

EN 1568 High,Medium,Low-expansion foam liquid foaming multiple and liquid separation time measuring instrument

Brand Name: Gold
Model Number: Gd-EN1568
MOQ: 1
Price: negotiation
Delivery Time: 60 works day
Payment Terms: L/C,D/P,D/A,T/T,Western Union
Detail Information
Place of Origin:
China
Certification:
ISO
Name:
High,Medium,Low-expansion Foam Liquid Foaming Multiple And Liquid Separation Time Measuring Instrument
Standard:
EN 1568 ,UL 162,NFPA 11
Test Area:
High,Medium,Low-expansion Foam Liquid Foaming Multiple And Liquid Separation Time
Liquid Separation Time:
25,50%
Operating Pressure Range:
0.3–0.65 MPa
Foam Material:
AFFF
Packaging Details:
plywood box
Supply Ability:
1 per 60 works days
Highlight:

EN 1568 foam liquid measuring instrument

,

foam expansion testing equipment

,

liquid separation time measurement device

Product Description
EN 1568 High, Medium, Low-Expansion Foam Liquid Testing Instrument
This precision testing instrument evaluates foam expansion ratio, 25% drainage time, and 50% drainage time for high-expansion, medium-expansion, and low-expansion foam solutions. Featuring stainless steel construction, high-precision flow control, and automated timing systems, it ensures accurate, repeatable results for foam concentrate manufacturers, fire safety laboratories, and regulatory compliance teams.
EN 1568 High,Medium,Low-expansion foam liquid foaming multiple and liquid separation time measuring instrument 0
Application Scope
Specifically designed for evaluating foam expansion ratio, 25% drainage time, and 50% drainage time of high-expansion, medium-expansion, and low-expansion foam solutions. The system supports international standards including ISO 7203-1-2, EN 1568-1-2-3, UL 162, and NFPA 11.
Compliance Standards
This equipment meets the following standards for determining foam expansion ratio and drainage times:
  • GB 15308-2006 "Foam Extinguishing Agents" - Sections 5.8 & 5.9
  • GB 19156-2019 "General Technical Conditions for Fire Monitors" - Section 6.4.4.1
  • GB 20031-2005 "Foam Fire Extinguishing Systems and Components" - Section 6.20.2
  • UL 162-2024 "Foam Equipment and Liquid Concentrates" - Section 10.2
  • EN 1568 Series:2018 "Fire extinguishing media - Foam concentrates"
  • NFPA 11-2024 "Standard for Low-, Medium-, and High-Expansion Foam"
  • ISO 7203 series:2019 "Fire extinguishing media - Foam concentrates"
Pressure Control
Proportional control valve and electromagnetic flowmeter ensure stable liquid supply pressure (0.3-0.65 MPa), compatible with ASTM D1881 test conditions.
Technical Specifications
System Composition
Standard compressed air foam system with high, medium, and low expansion foam collectors and foam separation tester.
Low-Expansion Foam System
  • Standard foam gun: Water flow rate (11.4±0.4)L/min at (0.63±0.03)MPa
  • Stainless steel foam collector
  • Brass liquid analyzer with 1 mL accuracy
EN 1568 High,Medium,Low-expansion foam liquid foaming multiple and liquid separation time measuring instrument 1 EN 1568 High,Medium,Low-expansion foam liquid foaming multiple and liquid separation time measuring instrument 2 EN 1568 High,Medium,Low-expansion foam liquid foaming multiple and liquid separation time measuring instrument 3 EN 1568 High,Medium,Low-expansion foam liquid foaming multiple and liquid separation time measuring instrument 4 EN 1568 High,Medium,Low-expansion foam liquid foaming multiple and liquid separation time measuring instrument 5
Medium-Expansion Foam System
  • Foam generator: Water flow rate (3.25±0.15) L/min at (0.5±0.01) MPa
  • 200L stainless steel foam collector (±2L accuracy)
  • 10mL graduated cylinder
  • 1℃ graduation thermometer
  • 0.1s graduation stopwatch
  • 0.01kg accuracy platform scale
EN 1568 High,Medium,Low-expansion foam liquid foaming multiple and liquid separation time measuring instrument 6 EN 1568 High,Medium,Low-expansion foam liquid foaming multiple and liquid separation time measuring instrument 7
High-Expansion Foam System
  • Foam generator: Water flow rate (6.1±0.1) L/min at (0.5±0.01) MPa
  • 500L stainless steel foam collector (±5L accuracy)
  • 10mL graduated cylinder
  • 1℃ graduation thermometer
  • 0.1s graduation stopwatch
  • 0.01kg accuracy platform scale
EN 1568 High,Medium,Low-expansion foam liquid foaming multiple and liquid separation time measuring instrument 8 EN 1568 High,Medium,Low-expansion foam liquid foaming multiple and liquid separation time measuring instrument 9
Accessories
  • Air compressor: 0.8MPa, 30L/min flow rate
  • Thermometer: 1℃ graduation mercury thermometer
  • Measuring cylinder: 500mL, 10mL graduation
  • Balance: 1000g/0.1g
  • Stopwatch: 0.1s graduation
Measurement Environment Requirements
  • Ambient temperature: 15-25℃
  • Foam temperature: 15-20℃