Good price  online

products details

Created with Pixso. Home Created with Pixso. Products Created with Pixso.
Environmental Testing Equipment
Created with Pixso. EN 1568 High,Medium,Low-expansion foam liquid foaming multiple and liquid separation time measuring instrument

EN 1568 High,Medium,Low-expansion foam liquid foaming multiple and liquid separation time measuring instrument

Brand Name: Gold
Model Number: Gd-EN1568
MOQ: 1
Price: negotiation
Delivery Time: 60 works day
Payment Terms: L/C,D/P,D/A,T/T,
Detail Information
Place of Origin:
China
Certification:
ISO
Name:
High,Medium,Low-expansion Foam Liquid Foaming Multiple And Liquid Separation Time Measuring Instrument
Standard:
EN 1568 ,UL 162,NFPA 11
Test Area:
High,Medium,Low-expansion Foam Liquid Foaming Multiple And Liquid Separation Time
Liquid Separation Time:
25,50%
Operating Pressure Range:
0.3–0.65 MPa
Foam Material:
AFFF
Packaging Details:
plywood box
Supply Ability:
1 per 60 works days
Highlight:

EN 1568 foam liquid measuring instrument

,

foam expansion testing equipment

,

liquid separation time measurement device

Product Description
EN 1568 High, Medium, Low-Expansion Foam Liquid Testing Instrument
This precision testing instrument evaluates foam expansion ratio, 25% drainage time, and 50% drainage time for high-expansion, medium-expansion, and low-expansion foam solutions. Featuring stainless steel construction, high-precision flow control, and automated timing systems, it ensures accurate, repeatable results for foam concentrate manufacturers, fire safety laboratories, and regulatory compliance teams.
EN 1568 Foam Testing Instrument
Application Scope
Specifically designed for evaluating foam expansion ratio, 25% drainage time, and 50% drainage time of high-expansion, medium-expansion, and low-expansion foam solutions. The system supports international standards including ISO 7203-1-2, EN 1568-1-2-3, UL 162, and NFPA 11.
Compliance Standards
This equipment meets the following standards for determining foam expansion ratio and drainage times:
  • GB 15308-2006 "Foam Extinguishing Agents" - Sections 5.8 & 5.9
  • GB 19156-2019 "General Technical Conditions for Fire Monitors" - Section 6.4.4.1
  • GB 20031-2005 "Foam Fire Extinguishing Systems and Components" - Section 6.20.2
  • UL 162-2024 "Foam Equipment and Liquid Concentrates" - Section 10.2
  • EN 1568 Series:2018 "Fire extinguishing media - Foam concentrates"
  • NFPA 11-2024 "Standard for Low-, Medium-, and High-Expansion Foam"
  • ISO 7203 series:2019 "Fire extinguishing media - Foam concentrates"
Pressure Control
Proportional control valve and electromagnetic flowmeter ensure stable liquid supply pressure (0.3-0.65 MPa), compatible with ASTM D1881 test conditions.
Technical Specifications
System Composition
Standard compressed air foam system with high, medium, and low expansion foam collectors and foam separation tester.
Low-Expansion Foam System
  • Standard foam gun: Water flow rate (11.4±0.4)L/min at (0.63±0.03)MPa
  • Stainless steel foam collector
  • Brass liquid analyzer with 1 mL accuracy
Low Expansion Foam System Installation Standard Foam Gun Schematic Standard Foam Gun Picture Low Expansion Foam Collector Liquid Separation Measuring Device
Medium-Expansion Foam System
  • Foam generator: Water flow rate (3.25±0.15) L/min at (0.5±0.01) MPa
  • 200L stainless steel foam collector (±2L accuracy)
  • 10mL graduated cylinder
  • 1℃ graduation thermometer
  • 0.1s graduation stopwatch
  • 0.01kg accuracy platform scale
Medium Expansion Foam System Installation Medium Expansion Foam Collector
High-Expansion Foam System
  • Foam generator: Water flow rate (6.1±0.1) L/min at (0.5±0.01) MPa
  • 500L stainless steel foam collector (±5L accuracy)
  • 10mL graduated cylinder
  • 1℃ graduation thermometer
  • 0.1s graduation stopwatch
  • 0.01kg accuracy platform scale
High Expansion Foam System Installation High Expansion Foam Collector
Accessories
  • Air compressor: 0.8MPa, 30L/min flow rate
  • Thermometer: 1℃ graduation mercury thermometer
  • Measuring cylinder: 500mL, 10mL graduation
  • Balance: 1000g/0.1g
  • Stopwatch: 0.1s graduation
Measurement Environment Requirements
  • Ambient temperature: 15-25℃
  • Foam temperature: 15-20℃