Brand Name: GOLD
Model Number: GD-EN 54-10
MOQ: 1set
Price: 4000-4233USD/set
Delivery Time: 30days
Payment Terms: L/C,D/A,D/P,T/T,Western Union,MoneyGram
Detail Information
Place of Origin:
China
Certification:
ISO
Product Name:
Infrared And Ultraviolet Flame Detector Testing Device
Standard:
En 54-10,ISO 7240,FM 3260
Test Area:
Infrared And Ultraviolet Flame Detectors
Laboratory Temperature:
15℃-35℃ (Around 25℃ Is Ideal)
Laboratory Space:
Length 3.8 Meters, Width 3.0 Meters
Power Supply:
AC220V 50Hz
Gas:
Methane
Detector Movement Range From Flame:
0-2500
Packaging Details:
Standard Wooden Case
Supply Ability:
5sets/Month
Product Description
ISO 7240-10 Infrared and Ultraviolet Flame Detector Calibrator Tester EN 54-10
Product Overview

This EN 54-10 UV/IR Flame Detector Tester is a professional functional testing device designed for field and laboratory testing of point flame detectors. It accurately simulates flame radiation signals and supports comprehensive testing protocols including response threshold measurement, consistency testing, repeatability testing, orientation testing, power-on testing, power supply parameter fluctuation testing, and ambient light interference testing.

The equipment supports testing of various flame detector types including UV, single/dual/triple-band IR, UV/IR combinations, and multispectral detectors.

Compliance Standards
  • EN 54-10 Fire detection and fire alarm systems - Part 10: Flame detectors - Point detectors
  • ISO 7240-10:2012 - Fire detection and alarm systems -- Part 10: Point-type flame detectors
  • FM 3260 - Approval Standard for Flame Radiation Detectors for Automatic Fire Alarm Signaling
  • GB12791-2006, GB15631-2008 Point-type infrared and ultraviolet flame detectors
Infrared and Ultraviolet Flame Detector Testing Device
Technical Specifications
Instrument Composition: Optical track, infrared and ultraviolet light source, neutral density filter, shutter, modulator, sample slide support
Optical Track: Dual-electric displacement track, effective length: 2.5m, movement measurement accuracy: ±4mm; Straightness: <0.04mm
Light Source: Utilizes methane combustion flame as infrared and ultraviolet light source
Fuel Gas: Methane with purity ≥99.9%
Radiant Energy Stability: Variation in light source radiant energy <±5%
Ignition Method: Remote-controlled high-voltage electronic ignition
Neutral Density Filter: Wavelength: 200nm-300nm, includes 50% and 60% physical neutral density filters
Modulator: Chopper with DC motor, frequency range: 0-14Hz continuously adjustable
Sample Slide Support: Height adjustable 10-200mm, angle adjustment accuracy: ±5°, movement speed: 50mm/s
Control System: Touch screen + PLC control with stepper motors for positioning
Power Supply: 50Hz, AC220V, 600W
Laser Alignment: Integrated laser beam for sample and light source alignment
UV/IR Flame Detector Tester
Testing Capabilities
  • Response threshold test
  • Consistency test
  • Repeatability test
  • Orientation test
  • Power-on test
  • Power parameter fluctuation test
  • Ambient light interference test
Environmental Requirements
Parameter Specification
Temperature 15ºC-35ºC (25ºC ideal)
Relative Humidity 25%-75% RH
Atmospheric Pressure 86-106 kPa
Environmental Conditions No direct sunlight, open flames, or strong airflow
Equipment & Facility Requirements
Dimensions: 2780mm × 530mm × 1370mm (L×W×H)
Total Power: AC220V, 600W
Power Supply: AC220V 50HZ (voltage fluctuation ≤ ±10%)
Methane: 99% purity methane (1 bottle), gas cylinder cabinet provided
Ventilation: Laboratory must be well-ventilated
Clearance: Minimum 600mm distance from walls