Good price  online

products details

Created with Pixso. Home Created with Pixso. Products Created with Pixso.
Fire Resistance Tester
Created with Pixso. UL162 Foam Extinguishing Agent Expansion Ratio And 25% Liquid Separation Time Tester

UL162 Foam Extinguishing Agent Expansion Ratio And 25% Liquid Separation Time Tester

Brand Name: GOLD
Model Number: GD-UL162
MOQ: 1 set
Price: USD3000-5000/set
Delivery Time: 30 days
Payment Terms: L/C,D/A,D/P,T/T,Western Union
Detail Information
Place of Origin:
China
Certification:
ISO
Product Name:
Low-Expansion Foam Expansion & Drainage Time Tester
Test Standard:
UL162,EN 1568-1,NFPA 11
Power Supply:
AC220V 50/60Hz 10A
Foam Gun Pressure:
(0.63-0.03)MPa
Foam Gun Flow Rate:
(11.4-;0.4)L/Min
Foam Temperature:
(15~20) Degree
Ambient Temperature:
(15~25) Degree
Foam Gun Stand Height:
Adjustable From 0.8 To 1.5m
Packaging Details:
Plywood case
Supply Ability:
5 sets per month
Highlight:

UL162 foam extinguishing agent tester

,

fire resistance expansion ratio tester

,

liquid separation time tester UL162

Product Description
UL162 Foam Extinguishing Agent Expansion Ratio And 25% Liquid Separation Time Tester
Product Description
This device is manufactured according to the requirements of GB/T15308 standard and is a foam generation system used in small-scale tests for foam performance quality control. It meets the requirements of GB/T15308 foam extinguishing agents, Appendix A.2 foam performance test standard clauses, GB 27897-2011 expansion ratio and 25% liquid separation time.
Compliance Standards
  • ISO 7203-1:2023 - Foam fire extinguishing media
  • EN 1568-1:2020 - Fire extinguishing media - Foam concentrates
  • UL 162:2022 - Standard for Foam Equipment and Liquid Concentrates
  • NFPA 11:2025 - Standard for Low-, Medium-, and High-Expansion Foam
  • ASTM D1881-21 - Standard Test Method for Foaming Properties of Surface-Active Agents
  • JIS K 4814:2020 - Foam fire extinguishing agents
  • AS 1851-2024 - Routine service of fire protection systems and equipment
UL162 Foam Extinguishing Agent Expansion Ratio And 25% Liquid Separation Time Tester 0
Technical Parameters
Name Low-expansion foam liquid foaming multiple and liquid separation time measuring instrument
Standard UL162, EN 1568-1, NFPA 11
Foam solution temperature 15℃ ~ 20℃
Ambient temperature 15℃ ~ 25℃
Foam generation system Consists of a 5L/min foam gun, 1.5-level (0-1) MPa pressure gauge, pressure tank, air compressor, etc.
Foam gun The flow rate measured using water at a pressure of 0.7 ± 0.03 MPa is (5.0 ± 0.1) L/min
Product Features
  • Composition: Consists of low-expansion foam generation system, standard foam gun, low-expansion foam collector, and low-expansion foam separation analyzer
  • Low-expansion foam generation system: Composed of air inlet pipe, pressure-resistant storage tank, pressure gauge, foam liquid delivery pipe, and adjustable support
  • Standard foam gun: When calibrated with water, at pressure of (0.63±0.03) MPa, water flow rate is (11.4±0.4) L/min
  • Low-expansion foam collector: Made of stainless steel
  • Liquid analyzer: Made of brass; used to calibrate volume of foam receiving tank to 1 mL with water
  • Accessories include air compressor, thermometer, graduated cylinder, balance, and stopwatch
UL162 Foam Extinguishing Agent Expansion Ratio And 25% Liquid Separation Time Tester 1 UL162 Foam Extinguishing Agent Expansion Ratio And 25% Liquid Separation Time Tester 2
Test Procedure

a) Prepare foam solution using fresh water according to required concentration. Control temperature to ensure produced foam temperature is within (15-20)℃.

b) Start air compressor and adjust inlet pressure of foam gun to (0.7±0.03) MPa. Wet inner wall of foam receiving tank, wipe clean, and weigh (m1).

c) After spraying for (5-10) seconds until stabilization, collect foam using eluent analyzer. Start stopwatch, scrape off overflowing foam, weigh (m2), and calculate mass of 25% eluent.

d) Remove receiving container from precipitation analyzer and place on balance. Place foam receiving container on support, ensuring precipitate is free of foam. Stop stopwatch when precipitated liquid reaches 25% of volume.

e) Calculate foaming ratio using specified formula.

UL162 Foam Extinguishing Agent Expansion Ratio And 25% Liquid Separation Time Tester 3